Select a calculation method, then enter the connected loads from the project plans and specifications to determine the required service size per NEC 2026 Article 120. Not sure which? Start with the Optional Method (NEC 120.82): it fits most single homes with a 100 A or larger service. Use the Standard Method when the Optional Method does not apply or your plan checker asks for it.
The Optional Method allows a simplified calculation for single dwelling units served by a single 120/240V or 208Y/120V, 3-wire set of service or feeder conductors with an ampacity of 100A or greater (NEC 120.82(A)). It totals general and fixed loads, applies 100% to the first 8 kVA and 40% to the remainder, and then adds the larger of the heating or cooling load per NEC 120.82(C).
NEC 2026: load calculations are in Article 120 (formerly Article 220). Use it only where the 2026 NEC is adopted.