GENERAL NOTES:
- COORDINATE WITH THE UTILITY SERVICE PLANNER TO CONFIRM AVAILABLE AIC RATING AND ELECTRICAL SERVICE DETAILS PRIOR TO FINALIZING ANY BIDS.
- ALL SERVICE EQUIPMENT SUPPLYING DWELLING UNITS SHALL BE EQUIPPED WITH A SURGE PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH NEC 230.67.
- LUGS SHALL BE SUITABLE FOR USE WITH COPPER OR ALUMINUM CONDUCTORS AND LISTED FOR USE WITH 75°C AMPACITY CONDUCTORS.
- ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA).
- PER NEC 2023 SECTIONS 210.19(A) AND 215.2(A)(1)(B), FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO LIMIT INDIVIDUAL VOLTAGE DROP TO 3%, WITH A MAXIMUM COMBINED VOLTAGE DROP OF 5%.
- THE GROUNDING SYSTEM SHALL PROVIDE LESS THAN 25 OHMS RESISTANCE TO GROUND AT THE SERVICE CONNECTION.
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
0
0
user
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
user2025-08-08 09:54:542025-09-07 08:10:26Single Family 400A, 120/240V
GENERAL NOTES:
- COORDINATE WITH THE UTILITY SERVICE PLANNER TO CONFIRM AVAILABLE AIC RATING AND ELECTRICAL SERVICE DETAILS PRIOR TO FINALIZING ANY BIDS.
- ALL SERVICE EQUIPMENT SUPPLYING DWELLING UNITS SHALL BE EQUIPPED WITH A SURGE PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH NEC 230.67.
- LUGS SHALL BE SUITABLE FOR USE WITH COPPER OR ALUMINUM CONDUCTORS AND LISTED FOR USE WITH 75°C AMPACITY CONDUCTORS.
- ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA).
- PER NEC 2023 SECTIONS 210.19(A) AND 215.2(A)(1)(B), FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO LIMIT INDIVIDUAL VOLTAGE DROP TO 3%, WITH A MAXIMUM COMBINED VOLTAGE DROP OF 5%.
- THE GROUNDING SYSTEM SHALL PROVIDE LESS THAN 25 OHMS RESISTANCE TO GROUND AT THE SERVICE CONNECTION.
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
0
0
user
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
user2025-08-08 09:52:232025-09-06 11:27:09Single Family 400A, 120/240V with seperate ADU meter
GENERAL NOTES:
- COORDINATE WITH THE UTILITY SERVICE PLANNER TO CONFIRM AVAILABLE AIC RATING AND ELECTRICAL SERVICE DETAILS PRIOR TO FINALIZING ANY BIDS.
- ALL SERVICE EQUIPMENT SUPPLYING DWELLING UNITS SHALL BE EQUIPPED WITH A SURGE PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH NEC 230.67.
- LUGS SHALL BE SUITABLE FOR USE WITH COPPER OR ALUMINUM CONDUCTORS AND LISTED FOR USE WITH 75°C AMPACITY CONDUCTORS.
- ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA).
- PER NEC 2023 SECTIONS 210.19(A) AND 215.2(A)(1)(B), FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO LIMIT INDIVIDUAL VOLTAGE DROP TO 3%, WITH A MAXIMUM COMBINED VOLTAGE DROP OF 5%.
- THE GROUNDING SYSTEM SHALL PROVIDE LESS THAN 25 OHMS RESISTANCE TO GROUND AT THE SERVICE CONNECTION.
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
0
0
user
http://zigtech.ai/wp-content/uploads/2025/07/Final_Orange02-1-1-300x92.png
user2025-08-08 09:48:442025-09-06 11:27:13Single Family 400A, 120/240V with ADU
GENERAL NOTES:
- COORDINATE WITH THE UTILITY SERVICE PLANNER TO CONFIRM AVAILABLE AIC RATING AND ELECTRICAL SERVICE DETAILS PRIOR TO FINALIZING ANY BIDS.
- ALL SERVICE EQUIPMENT SUPPLYING DWELLING UNITS SHALL BE EQUIPPED WITH A SURGE PROTECTIVE DEVICE (SPD) IN ACCORDANCE WITH NEC 230.67.
- LUGS SHALL BE SUITABLE FOR USE WITH COPPER OR ALUMINUM CONDUCTORS AND LISTED FOR USE WITH 75°C AMPACITY CONDUCTORS.
- ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA).
- PER NEC 2023 SECTIONS 210.19(A) AND 215.2(A)(1)(B), FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO LIMIT INDIVIDUAL VOLTAGE DROP TO 3%, WITH A MAXIMUM COMBINED VOLTAGE DROP OF 5%.
- THE GROUNDING SYSTEM SHALL PROVIDE LESS THAN 25 OHMS RESISTANCE TO GROUND AT THE SERVICE CONNECTION.